TOKYO KEIKI FLAT RADAR LEVEL SENSOR MRF-10

TOKYO KEIKI FLAT RADAR LEVEL SENSOR MRF-10


Specifications
Flat Radar Level Sensor MRF-10
General Measuring principle Time of Flight Impulse Radar Technology Operating frequency 5.8GHz Half power beam angle Lengthwise: 50°/ Crosswise: 23° Display /Configuration No display / Graphical PC Configuration available Electrical Power supply Loop-powered 16 ~ 36V DC Output Analog: 4-20mA + Digital: HART Protocol Output variable Level, Ullage (m or ft), Volume(%), Amplitude (dB) Signal on alarm Hold, Low (3.9mA), High (22mA) Others Arrester and 10m shielded twisted 3 - cores Cable are built-in. Mechanical Housing (Enclosure) Body: Casting stainless steel (316 equivalent)/Antenna face: FRP Size 172 x 192 x 54mm (without Cable gland) Mass Approx. 2.7kg (without Cable) Environment Ambient temperature -20℃ ~ 70℃ (-4°F ~ 158°F) Ambient pressure ATM Protection degree IEC 60529 IP68 (10m Depth /24hr.) Measuring Performance Accuracy ±5mm (0.1 - 5m range) ±10mm (5 - 10m range) Repeatability ±1mm Update interval 1sec Measuring range Up to 10m Max. Applicable circular channel: more than φ400mm
Details

Features
  1. IP68 submergible
    Stormwater will not break MRF-10 by under the water.
  2. Compact body (Height: 54mm)
    Height: 54mm, easy installation for narrow space like under the Manhole
  3. Loop-Powered
    Easy replacement to existing Loop-powered instrumentations
  4. HART communication
    HART protocol has been superimposed onto analog output
  5. Easy Configuration
    Graphical PC software by HART
  6. Simple one-piece structure
    No independent main console required

View more about TOKYO KEIKI FLAT RADAR LEVEL SENSOR MRF-10 on main site